Double insulated signal transmitters
General Description
MISCN-D – double insulated signal transducer converts
the input signal one to 2 isolated output signals
(420mA / 010 VDC) .kiim galvanic isolation between: entry ports; Input voltage inputs; Output port; Input voltage outputs.
MISCN-DI – two transducers are isolated in one package.
Minus the common entrances.
Specifications
Accuracy: + 0.1% FS Input: 24 +2 VDC inputs (to order): (4-20 mA (Rin = 15 Ohms or (one and two-by model) (VDC 0-10 (Rin> 10 MΩ ports 2 ports 4-20 mA (to order): (RLOAD MAX <560 Ω per port) or 2 outputs 0-10 VDC or 4-20 mA and a second 0-10 VDC. Attention !! 4-20mA Output active. not connect 24V Column galvanic isolation: up to 500 VDC between entry and exit; Input Voltage input; exit port; ports input voltage. Fuse inside: 0.25 A protection against input voltage rise. temperature environment: -20 ° C - +65 Packaging: plastic box NORYL . Dimensions: W 70 x H 73 x L90 mm. Connections: Connection by removable clamps (12 Blocks). Installation: on DIN strip. Waterproof: IP-54