Temperature Controller for broadband insallation MSCI-LCD-RTD
Description
MSCI-LCD displays value of inputs signal and provi-des C/O contact when the input signal is above set-point AL. Model MSCI-2-LCD has 2 output relays and available for DC input signal.
Specifications
Accuracy: +0.25% F.S. or ±1 count,
+0.5% F.S. for AC measuring
Power supply: 220VAC or 12/24V DC
Input: current / voltage DC /AC,
resistance (3 wire) up to 100 K.
(MSCI-RTD – PT-100 temp. sensor only).
(MSCI-2-LCD – current / voltage DC only).
Output: c/o contact 220V / 5A . Operation
mode (FSL or FSH) is selected by internal jumper.
Ambient Temp.: -20 +65 C
Display: 3.5 digits (0-199.9) LCD size 0.5″
Enclosure: W70 x L90 x H73 mm plastic case
Connection: plug-in terminals
Mounting: 35mm DIN-rail
Calibration
The device is calibrated according to customer requirements.
Set point “AL” can be adjusted by potentiometer Set located under the plastic front panel (open the plastic cover.) Pressing the pushbutton “Set” allows to display set-point value.
Min and max display can be adjusted by poten-tiometers ZERO and SPAN located under the plastic front panel. Adjust 0 by pot’ ZERO when input signal is min. Adjust max display by SPAN pot’ when input signal is maximum. Repeat calibration.